A thermal image records how equipment is behaving under a particular set of conditions. Understanding those conditions is often as important as the image itself.

Load changes what you can see

Consider a circuit rated at 50 A.

If it is carrying 40 A during an inspection, resistance at a deteriorating connection may generate enough heat to create a noticeable temperature difference.

If the same circuit is carrying only 5 A, the thermal signature may be much less obvious.

The underlying condition hasn’t necessarily changed. The amount of energy being dissipated as heat has.

This is particularly relevant to equipment with varying loads. A thermal image records what is happening at that point in time, under those operating conditions. It doesn’t show what happened yesterday when the equipment was heavily loaded or what will happen tomorrow when production increases.

Load therefore provides important context to a thermal image.

Temperature differences aren’t necessarily faults

Finding something hotter than its surroundings is useful information, but the temperature difference needs interpretation.

The comparison might be between phases, similar pieces of equipment, adjacent connections or previous measurements of the same component.

There are also legitimate reasons for components to operate at different temperatures.

The interesting question isn’t simply “What’s hot?” It is “Why is this different?”

Sometimes that leads to an electrical problem. Sometimes it doesn’t.

Sometimes the heat isn’t coming from the object

Thermal cameras measure infrared radiation rather than temperature directly. The characteristics of the surface being inspected therefore matter.

One particularly interesting example is shiny metal.

Low-emissivity surfaces can reflect infrared radiation from their surroundings. The resulting thermal image can make part of the surface appear hotter than it really is.

We encountered a good example involving a busbar connection that had been identified as a possible hot connection.

The connection itself wasn’t generating the apparent hot spot. The shiny metal surface was reflecting infrared energy from the thermographer.

Something appearing hot in a thermal image doesn’t necessarily mean that object is generating the heat.

What you notice before taking the thermal image

After years of carrying out thermal inspections, one of the more interesting observations has been how much useful information is found visually.

Opening electrical equipment for a thermal inspection means you are also getting an opportunity to look closely at its physical condition.

Signs of previous overheating, damaged equipment, contamination, deteriorated insulation, loose components and unusual modifications don’t require a thermal camera to be noticed.

Some of these observations explain something subsequently seen thermally. Others have no significant thermal signature at all.

This makes visual and thermal inspection complementary rather than interchangeable.

Thermal imaging is a snapshot

Probably the simplest way to think about an electrical thermal image is as a snapshot of how the equipment is behaving under a particular set of conditions.

It can show temperature patterns that are difficult or impossible to observe visually.

But it doesn’t directly tell you:

  • whether every electrical connection is sound
  • what the equipment will look like under a substantially different load
  • whether an apparent temperature difference is necessarily a fault
  • the underlying cause of every abnormal temperature pattern

Sometimes the next step is another thermal measurement. Sometimes it is measuring current, comparing phases, physically inspecting a connection or looking at the equipment’s operating history.

And sometimes nothing further is required.

One piece of the picture

Thermal imaging is particularly useful because electrical equipment can be assessed while operating. A developing issue may produce a thermal pattern before it results in equipment failure.

But the image is still one piece of information.

Load, equipment condition, ambient conditions, surface characteristics, previous measurements and ordinary visual observations can all add context.

That makes the most useful question when looking at a thermal image less: “Is there a hot spot?” and more: “What is this image actually telling us?”

To talk about thermal imaging on your site, contact us.