MIXER GENSET MAIN CIRCUIT BREAKER REPLACEMENT

Urgently replacing a failed mixer genset main circuit breaker to minimise production downtime.

Mining & resources · Newcastle · Industrial support · Breakdown support

New MCCB installed in the genset

Customer need

During three years of ongoing project support at a Newcastle construction site, the mixer genset’s 400A main circuit breaker (MCCB) failed to close, preventing the equipment from operating. Onsite testing identified unstable load-side voltages and significant dust contamination within the breaker enclosure.

What we did

  • Provided phone support and attended site to investigate the fault.
  • Tested the genset supply and confirmed the failed 400A main circuit breaker.
  • Urgently sourced and installed a replacement MCCB.
  • Replaced the dust-contaminated RCD module.
  • Tested and commissioned the mixer with the new MCCB installed.
  • Located and repaired a compressor controller fuse fault during commissioning.

How it helped

The fast repair allowed production to continue with minimal downtime. Thorough testing and commissioning confirmed the new MCCB was operating correctly and identified the secondary compressor fault, allowing the auxiliary equipment to be repaired at the same time.

Failed 400A main circuit breaker before replacement
Failed 400A main circuit breaker before replacement
Removed main circuit breaker showing heavy dust contamination
Removed main circuit breaker showing heavy dust contamination
Dust accumulated around the internal sections of the failed MCCB
Dust accumulated around the internal sections of the failed MCCB